5. [SVF128] SETTING
- Note: Every SVF128 digital vortex flowmeters has been set according to requirement before delivery, please do not change setting unless it is necessary and under correct instruction!
SVF128 series digital vortex flowmeter have digital setting and code setting. Use code setting to set parameters such as fluid type, compensation type and output signal. Use digital setting to set parameters related to a number, such as pipe size, flow range, factor.
5.1 How to set
5.1.1 Code setting
Under working status, to enter code setting, please hold “Enter button” then press “U-D button” at the same time. Please reference to picture 5.1.
Picture 5.1: Enter and quit code setting
When in code setting, the first row will display the reference number of the code setting, and the lower row will display the contents of this parameter. The digit that is flashing is the digit under the setting. Please reference to picture 5.2, which means C01=02, means fluid type is liquid.
Picture 5.2 Code setting
When under code setting, Now, the user can use “L-R button” to choose which digit on the displayer are to be set and use “R-D button” to switch the digit to 0~9 . The first time of pressing “Enter button” means to set the lower row. Press the “Enter button” again to check if the setting is available. If setting is available, the setting mode will be canceled and the display will not flash, then press “L-R button” or “U-D button” to set it again. When display is not flashing, pressure “Enter button” to save and go to next setting.
If want to quit the code set, same as entering, please hold the “Enter button” then press “U-D button” at the same time.
5.1.2 Digital setting
Under working status, to enter code setting, please hold “Enter button” then press “L-R button” at the
same time. Please reference to picture 5.3.
Picture 5.3: Enter or quit digital setting
When in digital setting, the first row will display the reference number of the digital setting, and the lower row will display the contents of this parameter. The digit that is flashing is the digit under setting. Please reference to picture 5.4, which means D001=1.60000, max pressure is 1.6 (unit according to other setting.)
Picture 5.4: Digital setting
When under digital setting, Now, user can use “L-R button” to choose which digit on the displayer are to be set , and use “R-D button” to switch the digit to 0~9 . The first time of pressing “Enter button” means to set the lower row. Press “Enter button” again to check if the setting is available. If setting is available, the setting made will be canceled and the display will not flash, then press “L-R button” or “U-D button” to set again. When display is not flashing, pressure “Enter button” to save and go to next setting.
If want to quit code setting, same as entering, please hold “Enter button” then press “U-D button” at the same time.
5.2 Setting list
Please check chart 5.1 and 5.2 for code and digital setting address list.
Chart 5.1: Code setting address
Code settingaddress |
Item |
Code |
Description of code |
01 |
Fluid |
00 |
Steam |
01 |
Gas |
||
02 |
Liquid |
||
02 |
Density compensation |
00 |
Volume flow display, no density compensation |
01 |
Density preset |
||
02 |
Pressure compensation (for saturated steam pressure not larger than 20Mpa |
||
03 |
Temperature compensation (For saturated steam) |
||
04 |
Temperature and pressure compensation (For superheated steam) |
||
05 |
ρ=A+BP (Pressure compensation) |
||
06 |
ρ=A+BT (Temperature compensation) |
||
07 |
AGA-NX-19 to calculate compressibility factor |
||
08 |
Temperature and pressure compensation to get normal condition flow rate of gas |
||
09 |
AGA-8 to calculate compressibility factor |
||
10 |
Air compressor output flow analysis |
||
05 |
Output |
01 |
Pulse (Please reference to D008 for K factor) |
02 |
4~20mA or HART@4~20mA |
||
03 |
200-1000HZ frequency output, set what to output in C06 |
||
04 |
frequency output for total flow, set factor in D013 |
||
06 |
4~20mA or 4~20mA@HART or 200-1000Hz output parameter |
00 |
Flow rate |
01 |
Temperature |
||
02 |
Pressure |
||
07 |
Damping |
01~99 |
1~99 seconds |
08 |
Instrument number |
00~99 |
For Modbus |
00~15 |
For Modbus or HART communication |
||
09
|
Baud rate
|
01 |
1200 no parity 1 stop bit |
02 |
1200 even parity 1 stop bit |
||
03 |
2400 no parity 1 stop bit |
||
04 |
2400 even parity 1 stop bit |
||
05 |
4800 no parity 1 stop bit |
||
06 |
4800 even parity 1 stop bit |
||
07 |
9600 no parity 1 stop bit |
||
08 |
9600 even parity 1 stop bit |
||
09 |
19200 no parity 1 stop bit |
||
10 |
19200 even parity 1 stop bit |
||
11 |
1200 odd parity 1 stop bit |
||
12
13 |
2400 odd parity 1 stop bit
4800 odd parity 1 stop bit |
||
14 |
9600 odd parity 1 stop bit |
||
15 |
19200 odd parity 1 stop bit |
||
16 |
38400 no parity 1 stop bit |
||
17 |
38400 even parity 1 stop bit |
||
18 |
38400 odd parity 1 stop bit |
||
19 |
57600 no parity 1 stop bit |
||
20 |
57600 even parity 1 stop bit |
||
21 |
57600 odd parity 1 stop bit |
||
22 |
115200 no parity 1 stop bit |
||
23 |
115200 even parity 1 stop bit |
||
24 |
115200 odd parity 1 stop bit |
||
10
|
Time unit for flow rate
|
00 |
/s |
01
02 |
/min
/h |
||
03 |
/day |
||
11
|
Mass unit
|
01 |
kg |
02 |
ton |
||
03 |
lb |
||
12
|
Volume unit for flow rate
|
01 |
m3 |
02 |
L |
||
03 |
ft3 |
||
04 |
US gal |
||
05 |
UK gal |
||
13
|
Pressure unit
|
01 |
Mpa |
02 |
Kpa |
||
03 |
Psi |
||
14 |
Temperature unit
|
01 | ℃ |
02 |
℉ | ||
03 |
K | ||
15 |
Right digits number for total flow
|
00~05
|
00:No right digits for total flow |
01~05:1~5 right digits for total flow |
|||
16 |
1st row display parameter
|
01 |
Flow rate |
02 |
Percentage of flow rate to flow range |
||
17 |
lower row display parameter
|
00 |
No display |
01 |
Total flow |
||
02 |
Temperature |
||
03 |
Pressure |
||
04 |
Density |
||
05 |
Frequency | ||
18 |
Density unit
|
01 |
Kg/m3 |
02 |
lb/ft3 |
||
19 |
Decimal of flow rate |
00~04 |
00: No right digits for flow rate 01~04: 1~4 right digits for flow rate |
20 | Decimal of temperature | 00~04 |
00: No right digits for temperature 01~04: 1~4 right digits for flow rate |
21 | Decimal of pressure | 00~04 |
00: No right digits for pressure 01~04: 1~4 right digits for pressure |
30 | Time space for circle display | 00~30 | 00:circle display off |
1~30:1~30 seconds between the display of different parameter | |||
31 | First parameter displayed in circle display | 00~05 |
00:circle display off 01~05:see chart 7.1 |
⫶ | ⫶ | ⫶ | …. |
35 | Last parameter displayed in circle display | 00~05 | Same as above |
38 | Sequence of float (under RS485 communication) | 01 | LL_LH_HL_HH |
02 | HH_HL_LH_LL | ||
03 | LH_LL_HH_HL | ||
04 | HL_HH_LL_LH | ||
47 | Password function | 00 | off |
01 | on | ||
48 | Set password | 00 | Keep the password |
01 | Change the password | ||
49 | Spectrum analyzing checking | 00 | Working status |
12 | spectrum analyzing checking | ||
50 | Total flow reset | 00 | Reset total flow to 0 |
01 | Default | ||
55 | Times of over total flow | 00~99 | For reading only |
60 | Restore to backup date | 06 | Restore to backup date |
61 | Save setting backup | 16 | Save current setting for backup |
- Note:
If the unit of flow rate is changed or measurement changed from flow rate to mass flow, users can reset the total flow to 0 or record the current total flow.
Total flow=(time of over total flow)* (max display of total flow)+(current total flow reading)
Chart 5.2: Digits setting address
Digital setting address |
Item |
Code |
Description of code |
001 |
Max pressure |
[-99999,999999] |
Max input/output pressure |
002 |
Min pressure |
[-99999,999999] |
Min input/output pressure |
003 |
Max temperature |
[-99999,999999] |
Max input/output temperature |
004 |
Min temperature |
[-99999,999999] |
Min input/output temperature |
005 |
Preset density |
(0,999999] |
When C02=01, the meter will use this density, unit according to setting |
008 |
K factor |
(0,999999] |
K factor according to calibration result, unit is pulses/Liter. Flow=3.6*freq/K |
009 |
Max flow rate |
(0,999999] |
unit is same as flow rate, Max/min flow rate of 4~20mA and 200~1000Hz output |
010 |
Min flow rate |
[0,999999] |
|
011 |
Max frequency |
[0,999999] |
Up-limit of frequency (Hz) output |
012 |
Min frequency |
[0,999999] |
Down-limit of frequency (Hz) output |
013 |
pulse factor for total flow |
(0,999999] |
used when freq output of total flow |
014 |
Ambient pressure |
(0,999999] |
Unit according to setting |
015 |
Pipe size |
(0,999999] |
unit is mm |
021 |
Cut off small signal |
[0,999999] |
unit is Hz |
022 |
Standard temperature |
[0,999999] |
unit is °C; for standard flow rate calculation |
023 |
Temperature of air compressor inlet |
[-40,999999] |
Unit is °C, for air compressor flow outlet analysis |
024 |
Pressure of air compressor inlet |
(0,999999] |
Unit is Mpa, for air compressor flow outlet analysis |
025 |
Temperature preset |
[-99999,999999] |
Unit is °C |
026 |
Resonance frequency starting frequency |
(0,999999] |
For high speed steam measure use |
027 |
Resonance frequency ending frequency |
(0,999999] |
For high speed steam measure use |
030 |
Relative density of compressibility factor |
[0.55,0.90] |
For calculation of compressibility factor of natural gas |
031 |
mol% of N2 and H2 |
[0,0.1] |
For calculation of compressibility factor of natural gas, eg.if 1%, please input 0.01 |
032 |
mol% of CO2 |
[0,0.3] |
For calculation of compressibility factor of natural gas, eg.if 1%, please input 0.01 |
033 |
Higher heating value |
[20,48] |
MJ/mol, For calculation of compressibility factor of natural gas |
Note: Max freq output=10KHz, the pulse factor for total flow should be set properly set according to the current total flow.
5.3 Example of setting
Sample: For vortex flowmeter SVF128, measure gas in DN50 pipe, K factor= 7.802P/L, density preset, mass flow display unit is kg/h. 4~20mA output with a flow range of 0~4000kg/hr
Code setting |
Address |
Code |
Description |
01 |
01 |
gas |
|
02 |
01 |
Density preset |
|
05 |
02 |
4~20mA analog output |
|
Digital setting |
005 |
2.0000 |
Density=2 |
008 |
7.802 |
K factor=7.802 P/L |
|
009 |
4000 |
Flow rate of 20mA |
|
010 |
0 |
Flow rate of 4mA |
|
015 |
50 |
Pipe size=50mm |
5.4 Password setting instruction
There is no password set in default in a new SVF128 digital vortex flowmeter ,users can set a password following instruction below.
Enter code setting, set C47=01, confirm and quit then enter the password setting interface as picture 5.5
Picture 5.5: Password setting interface
To set a new password, users have to input the correct password twice, the password will become effective only if the both inputs are the same; or users have to input again. If the power is off during a password setting process, the password will be 2000 as default. When a password becomes effective, users have to input the correct password before he can set the flowmeter, please reference to picture 5.6.
If users input incorrect password 3 times consistently, the display will come back to normal display
Picture 5.6: Password input